| Construction work | At least 3 monthly intervals by a competent person. | - Use the inbuilt test button (at least monthly).
- An operating time/current test by a competent person at least annually.
| - Use the inbuilt test button – immediately after it is connected and immediately before it used, first time each day.
- By a competent person, at least every 3 months.
|
| Manufacturing work | - If equipment is double insulated, at least every 12 months by competent person.
- If not double insulated, at least every 6 months by competent person.
and connected to a safety switch. | - Use the inbuilt test button – at least every 6 months.
- An operating time/current test at least every 12 months by competent person.
| - Use the inbuilt test button – daily or before each use, whichever is longer.
- By a competent person, at least every 12 months.
Note: From 1 March 2008, portable safety switches are not to be used in manufacturing work. Installed safety switches must be used. |
| Service work | At least 12 monthly intervals by a competent person or connected to a safety switch. | | |
| Office work | At least 5 yearly intervals by a competent person or connected to a safety switch. | - Use the inbuilt test button at least every 6 months.
- An operating time/current test by a competent person, at least every 2 years.
| - Use the inbuilt test button at least every 3 months.
- An operating time/current test by a competent person at least every 2 years.
|
| Amusement work (specified electrical equipment) | - If equipment is double insulated, at least every 12 months by competent person.
- If not double insulated, at least 6 months by competent person and connected to a safety switch.
| | |
| Amusement work (amusement rides and devices) | Inspected and tested each after each onsite assembly, and every six months. | | |
| Rural industry work (all plug in equipment) | Visual examination before each use. | | |
| Rural industry work (Specified electrical equipment used under stated electrical risk factors) | Either: test and inspect every 12 months or protect with a safety switch. | Recommended push button test every three months. | Recommended push button test every three months. |